คุณสมบัติ
DDS238-VAP type multi-function Protective Device is designed to measure single phase two wire AC active energy and used in overvoltage protection, under voltage protection and over-current protection . In case of over-voltage fault, under-voltage fault or over-current fault in line, this product can instantly power off the load to prevent electrical equipment from being burnt. The over-voltage, under-voltage and over-current values of this product can all be set up by yourself and can be adjusted on the basis of local practical condition .It is a long use-life product with the advantage of high stability , high over load capability , low power loss and wide working voltage range .
Product features
Feature:
Function mode and display code instruction
LCD Code |
Parameters setting |
default |
Max. |
Min. |
Marking |
de |
Function mode |
1 |
7 |
1 |
|
De1 |
Mode 1 |
|
|
|
overvoltage protection, under voltage protection and over-current protection automatic switch off/on |
De2 |
Mode 2 |
|
|
|
overvoltage protection, under voltage protection and over-current protection automatic switch off/manual switch on |
De3 |
Mode 3 |
|
|
|
Close function of overvoltage protection, under voltage protection and over-current protection ,always keep the output load switch off |
De4 |
Mode 4 |
|
|
|
Close function of overvoltage protection, under voltage protection and over-current protection ,always keep the output load switch on |
De5 |
Mode 5 , unit: second |
5 |
999 |
1 |
Close function of overvoltage protection, under voltage protection and over-current protection , keep the output load switch on /off in cycle |
De6 |
Mode 5 , unit: minute |
5 |
999 |
1 |
|
De7 |
Mode 5 , unit: hour |
5 |
999 |
1 |
|
Bg |
Backlight mode |
2 |
2 |
1 |
Mode 1 means always lighting,mode 2 means it will lighting last 30s after you push the button . it will light out after30s if no any operation with button |
SS |
Delay time in load switch on after input power on |
2s |
255s |
2s |
It means switch on the output load after how many times when product input power on again |
Uo |
Overvoltage protection value |
270V |
300 V |
85 V |
If the value exceed the range , the LCD will display off and closed this protection function |
UoH |
Overvoltage recovery value |
265 V |
300 V |
85 V |
This value must be smaller than overvoltage protection value. or it will default set as overvoltage protection value -5V when you save |
UL |
Under voltage protection value |
170 V |
300 V |
85 V |
If the value exceed the range , the LCD will display off and closed this protection function |
ULH |
Under voltage recovery value |
175 V |
300 V |
85 V |
This value must be smaller than under voltage protection value. or it will default set as under voltage protection value +5V when you save |
SU |
overvoltage / under voltage fault judgment time
|
3s |
60s |
0.1s |
It means the fault must be last how many times then it will make output load switch off when happen fault |
Io |
Over current protection value |
40A |
63 A |
1 A |
If the value exceed the range , the LCD will display off and closed this protection function |
Ic |
Malignant load protection value (Pure Resistive Load limit) |
0.5 A |
5 A |
0.5 A |
If the value exceed the range , the LCD will display off and closed this protection function |
SI |
Over current fault judgment time
|
3s |
60s |
0.1s |
It means the fault must be last how many times then it will make output load switch off when happen fault |
SH |
Delay time setting for recovery load after output load switch off protection |
60s |
512s |
1s |
It means the product must wait for how many times then make the output switch on again after happen protection |
op |
Delay time set for cycle switchunder function mode 5/6/7 |
5 |
999 |
1 |
The time unit is different under mode5/6/7 |
CL |
Delay time set for cycle switch onunder function mode 5/6/7 |
5 |
999 |
1 |
The time unit is different under mode5/6/7 |
Er1 |
Last five records of protection reason |
|
5 |
1 |
|
Note 1: Under voltage protection value must be smaller than Overvoltage recovery value , or it will restore factory setting
Note 2: Under the setting mode , mode 1 to 7 all can display the function mode , backlight mode , Delay time in load switch on after input power on , but the following display will difference according to the function mode.
Key operation instruction
LCD display instruction
Usage
Wire connection must connect as sequence of the above 2 type diagram
Note